HOME > 기술자료 > 수중케이블 연장시 적용표
| 기동 방식 |
출력(kw) | 전류(A) | 케이블사이즈(㎟ ) 상단220V , 하단380V or 440V | |||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 50m | 60m | 70m | 80m | 90m | 100m | 120m | 140m | 160m | 180m | |||
| 직입기동 | 0.75 | 3.5 2.0 |
0.75 0.75 |
0.75 0.75 |
1.25 0.75 |
1.25 0.75 |
2.0 1.25 |
2.0 1.25 |
2.0 1.25 |
2.0 2.0 |
3.5 2.0 |
1.5 2.0 |
| 1.5 | 7 4.0 |
1.25 0.75 |
1.25 0.75 |
2.0 1.25 |
2.0 1.25 |
3.5 2.0 |
3.5 2.0 |
3.5 2.0 |
3.5 2.0 |
5.5 3.5 |
5.5 3.5 |
|
| 2.2 | 11 6.5 |
2.0 1.25 |
2.0 1.25 |
3.5 2.0 |
3.5 2.0 |
3.5 2.0 |
3.5 2.0 |
5.5 3.5 |
5.5 3.5 |
8.0 5.5 |
8.0 5.5 |
|
| 3.7 | 18 10.5 |
3.5 2.0 |
3.5 2.0 |
3.5 3.5 |
5.5 3.5 |
5.5 3.5 |
5.5 3.5 |
8.0 5.5 |
8.0 5.5 |
14.0 8.0 |
14.0 8.0 |
|
| 5.5 | 26 15 |
5.5 3.5 |
5.5 3.5 |
5.5 3.5 |
8.0 5.5 |
8.0 5.5 |
8.0 5.5 |
14.0 8.0 |
14.0 8.0 |
14.0 8.0 |
14.0 8.0 |
|
| 7.5 | 34 12 |
5.0 3.5 |
5.5 3.5 |
8.0 5.5 |
8.0 5.5 |
14.0 8.0 |
14.0 8.0 |
14.0 8.0 |
22.0 14.0 |
22.0 14.0 |
22.0 14.0 |
|
| 11 | 48 28 |
8.0 5.5 |
14.0 8.0 |
14.0 8.0 |
14.0 8.0 |
22.0 14.0 |
22.0 14.0 |
22.0 14.0 |
22.0 14.0 |
30.0 22.0 |
30.0 22.0 |
|
| 15 | 65 37 |
14 8 |
14 8 |
14 8 |
22 14 |
22 14 |
22 14 |
22 14 |
30 22 |
38 22 |
38 22 |
|
| 19 | 75 38 |
14 8 |
22 14 |
22 14 |
22 14 |
22 14 |
30 14 |
30 22 |
38 22 |
50 22 |
50 30 |
|
| 22 | 85 49 |
22 14 |
22 14 |
22 14 |
30 14 |
30 14 |
30 22 |
30 22 |
38 30 |
50 30 |
50 30 |
|
| 스타 델타 기동 | 11 | 48 28 |
5.5 3.5 |
5.5 3.5 |
5.5 3.5 |
8.0 5.5 |
8.0 5.5 |
14 8 |
14 8 |
24 8 |
22 8 |
22 14 |
| 15 | 65 37 |
8.0 5.5 |
8.0 5.5 |
8.0 5.5 |
14 8 |
14 8 |
24 8 |
22 8 |
22 14 |
22 14 |
22 14 |
|
| 19 | 75 38 |
8.0 5.5 |
8.0 5.5 |
14 8 |
14 8 |
14 8 |
14 8 |
14 14 |
22 14 |
30 14 |
30 14 |
|
| 22 | 85 89 |
8.0 5.5 |
14 5.5 |
14 8 |
14 8 |
22 8 |
22 14 |
22 14 |
30 14 |
30 22 |
30 22 |
|
| 26 | 100 58 |
14 8 |
14 8 |
14 8 |
22 8 |
22 14 |
22 14 |
30 14 |
30 22 |
38 22 |
38 22 |
|
| 30 | 115 66 |
14 8 |
14 8 |
22 8 |
22 14 |
22 14 |
30 14 |
30 22 |
38 22 |
38 22 |
50 22 |
|
| 37 | 140 81 |
22 14 |
22 14 |
22 14 |
22 14 |
30 14 |
30 14 |
38 22 |
50 22 |
50 22 |
50 22 |
|
| 45 | 185 107 |
22 14 |
22 14 |
30 14 |
30 14 |
38 14 |
38 22 |
50 22 |
60 30 |
60 30 |
- - |
|
| 55 | 220 127 |
30 14 |
30 14 |
30 14 |
38 22 |
38 22 |
50 22 |
60 30 |
- - |
- - |
- - |
|
| 75 | 300 173 |
38 22 |
38 22 |
50 22 |
50 30 |
60 30 |
60 30 |
- - |
- - |
- - |
- - |
|

전선에 단면적은 표준 Voltage에서 2%이상 Drop되도록 결정되어야 하고 이 전압 강하는 다음 방식으로 계산된다.